Home/RGS tanks

Horizontal steel RGS tanks

Above-ground and underground, single- and double-wall vessels from 3 to 100 m³ for fuel, lubricants, water and process liquids.

Within an hourreply with a technical and commercial proposal for standard RVS and RGS tanks
In 30 daysfirst shipment for erection — you don’t wait for the whole batch
60–180 daysturnkey project: from design to commissioning
24 monthswarranty on manufacturing and erection

What we do

We manufacture horizontal steel tanks for diesel fuel, gasoline, oils, water, process liquids and food media. Above-ground and underground, single- and double-wall, with compartments and with ready-made process piping.

Horizontal tanks are advantageous where height is a constraint: they do not need a heavy foundation for a high point load, are easier to transport and are erected within days.

Designs

  • RGSN — above-ground, on saddle supports
  • RGSP — underground, with a process manhole shaft
  • Double-wall — the interstitial space is monitored for leaks; mandatory for filling stations and environmentally sensitive sites
  • Divided into compartments — several fuel types in one vessel
  • With heating, insulation, pump group and loading unit
Horizontal tank with manholes, piping and service platform
Volume
3 – 100 m³
Location
above-ground, underground
Walls
single-wall, double-wall
Steel grades
St3sp5, 09G2S, stainless
Warranty
24 months
Lead time
from 20 days
Standard sizes

RGS tank dimensions

Above-ground design, the most common range. Weights are given for single-wall and double-wall versions.

TypeVolume, m³Diameter, mmLength, mmSingle-wall weight, kgDouble-wall weight, kg
RGS-331,4102,4668001,800
RGS-551,8102,4001,2002,200
RGS-10102,0103,8801,8122,840
RGS-15152,0105,3802,2113,700
RGS-20202,4105,5202,7634,645
RGS-25252,4107,2203,4995,645
RGS-30302,4108,2203,8856,595

Tanks of 40, 50, 60, 75 and 100 m³ are made to order — dimensions differ noticeably between designs, so we confirm them at the calculation stage. Underground designs have a greater overall height because of the process manhole shaft.

What we take into account in the calculation

For underground tanks

Groundwater level, burial depth and backfill load determine the wall thickness and whether anchoring is needed. A tank that floats up in spring costs far more than a correct calculation done at the start.

Anti-corrosion protection

For underground tanks — a reinforced, heavy-duty coating, often combined with electrochemical protection. For above-ground tanks, primer and enamel over a prepared surface are sufficient.

What to send for the calculation

  • Volume and the stored product
  • Above-ground or underground
  • Single-wall or double-wall
  • Number of compartments, if needed
  • Installation region
  • Whether piping, pumps and a loading unit are required

Need a calculation for your project?

Send the technical specification or describe the task — we will reply with a calculation within an hour.

Submit a request Download the questionnaire (RU)